The
All-Purpose Gas Transport, Storage and Supply Vessels
180
and 230 Liters at 24 bar
| Easy
to Use
- Ideal
for transportable or stationary gas supply
- Automatic
pressure building and gas economizer systems
- All valves
and instruments within easy reach and visibility
- Stable
low center of gravity
- European
Ready ... TPED coded
Superior
Performance
- Rugged,
maneuverable and fast filling
- Gas and/or
liquid withdrawal
- Continuous
flow rates up to 10,5 Nm³/h
Cost
Effective
- Super-insulation
provides long holding time and low Nominal Evaporation Rate
- All stainless
steel vessels and patented inner support system for durability
and long life
- Heavy-duty
footring and large diameter handling ring with four supports
|

EC230SB
shown with
optional caster base
and towing handle
|
| 
|
LCCM
Models
- Dual
function regulator controls pressure building and gas economizing
- Eliminates
copper piping and fittings
- Easy
to set and adjust pressure-control knob
|
Flow
Schematic
 |
Item |
Plumbing
Controls and Function |
| 1 |
Gas Use Valve — Used for gas withdrawal. |
| 2 |
Fill
/ Liquid Valve — Used for filling or liquid withdrawal. |
| 3 |
Pressure
Control Valve — Used to turn on / off the pressure control
regulator function. |
| 4 |
Vent
Valve — Used to vent pressure. |
| 5 |
Combination
Pressure Control Regulator — Used to automatically control
operating pressure. |
| 6 |
Pressure
Gauge — Indicates internal cylinder pressure. |
| 7 & 8 |
Dual Pressure Relief Valves — Used to limit pressure in
the liquid cylinder. |
| 9 |
Liquid
Level Gauge — Used to approximate the liquid contents of
the liquid cylinder. |
Technical
Specification
| Type |
-f |
180
/ 24 |
230/24
RB |
230/24
SB* |
| Capacity |
f |
f |
f |
| Liquid
(gross) |
(liters) |
196 |
240 |
| Liquid
(net) |
(liters) |
186 |
228 |
| Gas
(N2)** |
(Nm³) |
98 |
120 |
| Gas
(O2)** |
(Nm³) |
126 |
154 |
| Gas
(Ar)** |
(Nm³) |
123 |
151 |
| Gas
(CO2)** |
(Nm³) |
104 |
128 |
| Gas
(N2O)** |
(Nm³) |
96 |
118 |
| Performance |
f |
f |
f |
| NER***
(N2) |
(%
per day) |
1,9 |
1,8 |
| NER
(O2 - AR) |
(%
per day) |
1,3 |
1,2 |
| NER
(CO2 - N2O) |
(%
per day) |
0,5 |
0,5 |
| Gas
Flow (N2, O2, Ar) |
(Nm³/hr) |
9,2 |
10,5 |
| Gas
Flow (CO2 or N2O) |
(Nm³/hr) |
2,9 |
2,9 |
| Relief
Valve Setting |
(bar) |
24 |
24 |
| Code |
f |
TPED
(EN1251) |
TPED
(EN1251) |
| Dimensions |
f |
f |
f |
| Tank
Diameter |
(mm) |
508 |
660 |
| Base
Type |
f |
footring |
round
with 5 casters |
mini-pallet |
| Base
Size |
(mm) |
508 |
660 |
715x715 |
| Height |
(mm) |
1622 |
1392 |
1389 |
| Empty
Weight |
(kg) |
135 |
170 |
189 |
| Maximum
Full Weight****, N2 |
(kg) |
285 |
354 |
373 |
| O2 |
(kg) |
347 |
430 |
449 |
| Ar |
(kg) |
394 |
488 |
507 |
| CO2 |
(kg) |
354 |
439 |
458 |
| N2O |
(kg) |
331 |
410 |
429 |
*
Option: Casters and towing handle (adds approximately 130 mm to overall
height and 10 kg to overall weight)
** At 10 bar pressure
*** NER = Nominal Evaporation Rate
**** Tank plus product at saturated pressure 0 bar for O2, N2, Ar
and triple point for CO2 and N2O
|